DOCUMENT NO: ASTP 5012 VERSION: 2006-03-23 Page 1 of 1
TITLE: Flame Resistant Cables & Splices under 30CFR Part 7
1.0 PURPOSE
To identify areas of the Code of Federal Regulations Title 30 (30CFR) Part 7, Subpart K, that requires clarification, in order to conduct consistent and appropriate flame testing.
2.0 SCOPE
30CFR Part 7, Subpart K.
3.0 REFERENCES
Title 30, Code of Federal Regulations.
4.0 DEFINITIONS
No items need defined.
5.0 TEST EQUIPMENT
As listed in 30CFR Part 7.406.
6.0 TEST SAMPLES
Samples are described in 30CFR Parts 7.407 and 7.408, with the following
modification. The test samples need not be humidity conditioned. A “Memorandum for the Record” dated July 18, 2005, and signed by Kenneth Sproul, Chief, Quality Assurance/Materials Testing Division, explains why humidity conditioning is not necessary. A copy of the memorandum is attached as “Appendix 1.”
7.0 PROCEDURES
As listed in 30CFR Parts 7.407 and 7.408.
8.0 TEST DATA
Test data from the applicant will be maintained with the applicant’s approval file; test data from a product audit will be maintained with the audit file.
9.0 PASS/FAIL CRITERIA
30CFR Parts 7.407 and 7.408 list the pass/fail criteria.
ASTP5012.doc Print Date: 3/29/2006
PRINTED AND ELECTRONIC COPIES OF THIS DOCUMENT ARE
UNCONTROLLED. VERIFY CORRECT VERSION PRIOR TO USE. TSTP0001, Rev 01